The following guide is for users who require guidance on their choice of isolator for a new installation. For a given application the choice is between DIN-rail mounting (MTL5000/MTL5500 Series) and backplane mounting (MTL4000/MTL4500 Series) devices.
If additional guidance is required, contact your local MTL representative.
|
|
|
Analogue Input - 2-wire transmitters, 4-20mA conventional and 'smart'
|
| Device |
No. of channels
|
Output to hazardous area
|
Important features |
| DIN-rail mounting devices |
| MTL5541 |
|
16.5V min. @ 20mA
|
Compatible with most smart transmitters
|
| MTL5541A |
1 |
8.6V diode |
4 wire smart transmitters |
| MTL5541AS |
1 |
8.6V diode |
4 wire smart transmitters, current sink output |
| MTL5544 |
2 |
16.5V min @ 20mA
|
Compatible with most smart transmitters
|
| MTL5544A |
2
|
8.6V diode |
4 wire smart transmitters |
| MTL5544AS |
2 |
8.6V diode |
4 wire smart transmitters, current sink output |
| MTL5544D |
1 |
16.5V min @ 20mA |
Compatible with most smart transmitters, repeat output
|
| MTL5544S |
2 |
16.5V min @ 20mA |
Compatible with most smart transmitters, current sink output
|
| Backplane mounting devices |
| MTL4541 |
1 |
16.5V min @ 20mA |
Compatible with most smart transmitters |
| MTL4541A |
1 |
8.6V diode |
4 wire smart tranmitters
|
| MTL4541AS |
1 |
8.6V diode |
4 wire smart transmitter, current sink output
|
| MTL4541B |
1 |
16.5V min @ 20mA |
As MTL4541 but adapted for MTL4041B substitution on legacy backplanes
|
| MTL4541P |
1 |
17.6V min @ 20mA |
As MTL4541B but with a higher power output, MTL4041P substitution on legacy backplanes
|
| MTL4541S |
1 |
16.5V min @ 20mA |
Suitable for conventional and smart transmitters, current sink output
|
| MTL4544 |
2 |
16.5V min @ 20mA |
Compatible with most smart transmitters |
| MTL4544A |
2
|
8.6V diode |
4 wire smart transmitters
|
| MTL4544AS |
2 |
8.6V diode |
4 wire smart transmitters, current sink output
|
MTL4544B
|
1 |
16.5V min @ 20mA |
As MTL4544 but adapted for MTL4044B substitution on legacy backplanes |
| MTL4544D |
1 |
16.5V min @ 20mA |
Compatible with most smart transmitters, repeat output |
|
|
|
Analogue Input - vibration transducer
|
| Device |
No. of channels |
Signal monitored |
Main features |
| DIN-rail mounting devices |
|
| MTL5531 |
1 |
Vibration transducer |
Compatible with vibration and accelerometer transducers
|
| MTL5533 |
2 |
Vibration transducer |
Compatible with vibration and accelerometer transducers |
| Backplane mounting devices |
| MTL4531 |
1 |
Vibration transducer |
Compatible with vibration and accelerometer transducers
|
| MTL4533 |
2 |
Vibration transducer |
Compatible with vibration and accelerometer transducers
|
|
|
|
Analogue - loop isolator
|
| Device |
No. of channels |
Output to hazardous area |
Main features |
| DIN-rail mounting devices |
| MTL5040 |
1 x AI + 1 x AO |
16.5V @ 20mA Vmax 11V @ 20mA |
Analogue input and output module |
|
|
|
Analogue Input - thermocouple and mV sources
|
| Device |
No. of channels |
Output to safe area |
Main features |
| DIN-rail mounting devices |
| MTL5575 |
1 |
4/20mA |
Configurable, built-in CJC, early burnout detection facility |
| MTL5576-THC |
2 |
4/20mA |
Configurable, built-in CJC, also config as 1in 2 out
|
| MTL5081 |
1 |
0 to ±50mV |
Selectable upscale or downscale |
| Backplane mounting devices |
| MTL4575 |
1 |
4/20mA |
Configurable, built-in CJC, early burnout detection facility |
| MTL4576-THC |
2 |
4/20mA |
Configurable, built-in CJC, also config as 1in 2 out |
| MTL4081 |
1 |
0 to ±50mV |
Selectable upscale or downscale |
|
|
|
Analogue Input - 2, 3 and 4-wire RTDs
|
| Device |
No. of channels |
Output to safe area |
Main features |
| DIN-rail mounting devices |
| MTL5575 |
1 |
4/20mA |
Configurable |
| MTL5576-RTD |
2
|
4/20mA |
Configurable, also config as 1in 2 out
|
| MTL5082 |
1 |
10 to 400 ohm |
Independent selection of 2, 3 or 4-wire RTDs on safe and hazardous area sides |
| Backplane mounting devices |
| MTL4575 |
1 |
4/20mA |
Configurable, many sensor types and ranges |
| MTL4576-RTD |
2 |
4/20mA |
Configurable, also config as 1in 2 out
|
|
|
|
Analogue Input - strain-gauge bridges
|
| Device |
No. of channels |
Output to safe area |
Main features |
| Backplane mounting devices |
| MTL4081 |
1 |
0 to ±50mV |
For monitoring bridge voltage |
| MTL4083 |
1 |
0 to +12V |
Can be used with MTL4081 for monitoring bridge supply |
|
|
|
Analogue Output - controller outputs, I/P converters
|
| Device |
No. of channels
|
Output to hazardous area
|
Important features |
| DIN-rail mounting devices |
| MTL5546 |
|
1mA <Io<24mA Vmax = 16V
|
Suitable for HART valve positioners, SC & OC LFD |
| MTL5546Y |
1 |
1mA <Io<24mA Vmax = 16V |
Suitable for HART valve positioners, OC LFD |
| MTL5549 |
2 |
1mA <Io<24mA Vmax = 16V |
Suitable for HART valve positioners, SC & OC LFD |
| MTL5549Y |
2
|
1mA <Io<24mA Vmax = 16V |
Suitable for HART valve positioners, OC LFD |
| Backplane mounting devices |
| MTL4546 |
1 |
1mA <Io<21.4mA Vmax = 16V |
Suitable for HART valve positioners, SC & OC LFD |
| MTL4546Y |
1 |
1mA <Io<26mA Vmax = 16V |
Suitable for HART valve positioners, OC LFD |
| MTL4549 |
2
|
1mA <Io<26mA Vmax = 16V |
Suitable for HART valve positioners, SC & OC LFD |
| MTL4549Y |
2
|
1mA <Io<24mA Vmax = 16V |
Suitable for HART valve positioners, OC LFD |
|
|
|
Digital Input - switches / proximity detectors
|
| Device |
No. of channels
|
Output to safe area
|
Important features |
| DIN-rail mounting devices |
| MTL5510 |
4 |
4 x solid state |
Can switch +ve or –ve polarity signals |
| MTL5510B |
4 |
4 x solid state |
Mult-function selectable |
| MTL5511 |
1 |
1 x SPDT |
Switch/proximity detector repeater |
| MTL5513 |
2 |
2 x solid state |
dc to 1kHz frequency response |
| MTL5514 |
1 |
1 x SPDT 1 x SPDT |
Switch/proximity detector repeater Independent LFD output |
| MTL5516C |
2 |
2 x SPDT |
Switch/proximity detector repeater |
| MTL5517 |
2 |
2 x SPDT 1 x SPDT |
Switch/proximity detector repeater Independent LFD output |
| MTL5014 |
2 |
1 x SPDT 1 x SPDT |
Switch/proximity detector repeater Phase reversal, selectable repeat output or LFD alarm |
| Backplane mounting devices |
| MTL4510 |
4 |
4 x solid state |
Can switch +ve or –ve polarity signals |
| MTL4510B |
4 |
4 x solid state |
Mult-function selectable switches +ve, -ve or ac signals
|
| MTL4511 |
1 |
1 x SPDT |
Switch/proximity detector repeater |
| MTL4513 |
2 |
2 x solid state |
dc to 1kHz frequency response switches +ve, -ve or ac signals
|
| MTL4514 |
1 |
1 x SPDT 1 x SPDT |
Switch/proximity detector repeater Independent LFD output |
| MTL4516 |
2 |
2 x SPST |
Switch/proximity detector repeater |
| MTL4516C |
2 |
2 x SPDT |
Switch/proximity detector repeater |
| MTL4517 |
2 |
2 x SPST 1 x SPDT |
Switch/proximity detector repeater Independent LFD output |
|
|
|
Digital Input - switch/proximity detectors, SIL3
|
| Device |
No. of channels |
Signals monitored |
Important features |
| DIN-rail mounting devices |
| MTL5501-SR |
1 |
24V logic |
Safety related, SIL3 certified
|
| Backplane mounting devices |
| MTL4501-SR |
1 |
24V logic |
Safety related, SIL3 certified
|
|
|
|
Digital Output - alarms, LEDs, solenoid valves, etc
|
| Device |
No. of channels
|
Output to hazardous area
|
Important features |
| DIN-rail mounting devices |
| MTL5521 |
1 |
12.8V<Vo<24V Imax = 48mA |
IIC gas groups, loop powered |
| MTL5522 |
1 |
9.9V<Vo<21.4V Imax = 70mA |
IIB gas groups, loop powered |
| MTL5523 |
1 |
12.8V<Vo<24V Imax = 48mA |
Independent LFD output |
| MTL5524 |
1 |
12.8V<Vo<24V Imax = 48mA |
Safety override feature, separately powered |
| MTL5525 |
1 |
7V<Vo<24V Imax = 48mA |
Safety override, low power output |
| Backplane mounting devices |
| MTL4521 |
1 |
12.8V<Vo<24V Imax = 48mA |
Loop powered |
| MTL4521L |
1 |
10.3V<Vo<24V Imax = 48mA |
Loop powered |
MTL4523 MTL4523R |
1 |
12.8V<Vo<24V Imax = 48mA |
Independent LFD output |
| MTL4523L |
1 |
12.8V<Vo<24V Imax = 48mA |
Loop powered, independent LFD output |
MTL4524 & MTL4524S |
1 |
12.8V<Vo<24V Imax = 48mA |
Safety override feature, separately powered |
| MTL4525 |
1 |
7V<Vo<24V Imax = 48mA |
Safety override, low power output |
|
|
|
Digital Output - switch output to hazardous area
|
| Device |
No. of channels |
Signals monitored |
Important features |
| DIN rail mounting devices |
|
| MTL5526 |
1 or 2 |
2 x DPDT |
Safe-area switch input or loop powered. 2ch or 1ch with 2 outputs |
| Backplane mounting devices |
| MTL4526 |
1 or 2
|
2 x DPDT |
Safe-area switch input or loop powered. 2ch or 1ch with 2 outputs
|
|
|
|
Pulse Input - turbine / flowmeters
|
| Device |
No. of channels
|
Input from hazardous area
|
Important features |
| DIN-rail mounting devices |
| MTL5532 |
1
|
Switch, proximity detector, current pulse, voltage pulse
|
Voltage and current inputs from 2 or 3-wire transmitters configurable 4-20mA analogue output
|
| MTL5541 |
1 |
2-wire pulse |
e.g. 2-wire turbine and vortex flowmeters |
| Backplane mounting devices |
| MTL4513 |
2 |
Switch, proximity detector |
e.g. 2-wire positive displacement flowmeters |
| MTL4532 |
1 |
1mA <Io<21.4mA Vmax = 16V |
Voltage and current inputs from 2 or 3-wire transmitters configurable 4-20mA analogue output
|
| MTL4541 |
1 |
2-wire pulse |
e.g. 2-wire turbine and vortex flowmeters |
|
|
|
Fire / Smoke detectors
|
| Device |
No. of channels |
Output to hazardous area |
Important features |
| DIN-rail mounting devices |
| MTL5561 |
2 |
Loop powered |
0–40mA, fire and smoke detectors |
| Backplane mounting devices |
| MTL4561 |
2 |
Loop powered |
0–40mA, fire and smoke detector |
|
|
|
Signal transfer - safe area to safe area - via hazardous area
|
Device pair |
No. of channels |
Signal transferred |
Important features |
| DIN-rail mounting devices |
MTL5546Y & MTL5541A |
1 |
4/20mA smart
|
Driver Receiver
|
MTL5526 & MTL5516C |
2 |
Status signals |
Driver Receiver |
MTL5051 & MTL5051 |
1 |
RS232 or RS422 |
Either can be used as receiver or driver |
| Backplane mounting devices |
MTL4546Y & MTL4541A |
1 |
4/20mA smart
|
Driver Receiver |
MTL4526 & MTL4516 |
2 |
Status signals |
Driver Receiver |
|
|
|
Trip amplifiers
|
| Device |
No. of channels |
Signals monitored |
Important features |
| DIN-rail mounting devices |
| MTL5314 |
1 |
4/20mA |
Configurable, one or two alarms |
|
|
|
Earth-leakage detector
|
| Device |
No. of channels |
Output to safe area |
Important features |
| Backplane mounting devices |
| MTL4220 |
8 |
1 x SPST |
Can monitor up to 8 loops, use BPS04 or 08 backplane
|
|
|
|